: 50 Max. load current: 80 mA, Internal voltage drop: 2 V or less ES: Analog output: 1 to 5 V or 0 to 10 V Output impedance: 1 k FS: Analog output: 4 to 20 mA Max. load impedance: 600 Min. load impedance: 50 PNP + External input selected PF3A7H--ES/FSNPN + External input selected PF3A7H--CS/DSBrown DC(+) Brown DC(+) Load Main circuit Main circuit Black OUT Black OUT Load 24 VDC 24 VDC

[F 5] [ FnC] Select FUNC (switching Analogue output 2/ External input) [ oUt] Analogue output PF3A706H Equivalent to M5 3 Nm10% 8 PF3A712H 9 Equivalent to M6 5.2 Nm10% : Arbitrary display mode can be added to the sub display by setting the [F10] sub display.

(For accumulated increment) [H_1 ] Setting of Hysteresis [ 300] 300 L/min (PF3A706H) Do not use the product in a place where static electricity is a problem. Otherwise it can cause failure or malfunction of the system.

(JJ 3 0 0 Maximum Stroke :r 0 (mm) ~ -XAO , Change of rod end shape ~li1~ " Spacial port position ,Xli18l;' With rod end bracket ~XC14 Change of trunnion bracke1 mounting position -Xe15, Change of lie-rod length 'XC26 Double cleVIS pm/Double knuckle pin with Ma'~im 'um strOke , , ,' " ::l bracket " c.

Rated Flow Range: 06 (60 to 6000 l/min), Thread Type: F [G (ISO 1179-1 Compliant)], Port Size: 14 (1 1/2), Output Specifications: ES (Out: PNP; Func: Analog Voltage Ouput <-> External Input)

Rated Flow Range: 60 to 6000 l/min, Thread Type: F [G (ISO 1179-1 Compliant)], Port Size: 1 1/2, Output Specifications: Out: PNP; Func: Analog Voltage Ouput <-> External Input, Lead Wire: -, Unit Specification: -, Calibration Certificate: -

(Refer to the table below) Default setting Model (Output specification) OUT1 OUT2 A NPN NPN B PNP PNP C NPN Analogue 1 to 5 V D NPN Analogue 4 to 20 mA E PNP Analogue 1 to 5 V F PNP Analogue 4 to 20 mA L PNP L2 PNP PNP L3 PNP Analogue 1 to 5 V L4 PNP Analogue 4 to 20 mA -35No.PF-OMZ0002-A [F 0] Selection of reference condition, unit selection function, switch output specifications.

: 1.5 V or less PFMC7###-##-L2#-### NPN type Maximum applied voltage: 28 V Maximum load current: 80 mA Internal voltage drop: 1.5 V or less -21No.PF-OMY0002 PFMC7###-##-L3/L4#-### NPN type Maximum applied voltage: 28 V Maximum load current: 80 mA Internal voltage drop: 1.5 V or less L3: Analogue output: 1 to 5 V or 0 to 10 V Output impedance: 1 k L4: Analogue output: 4 to 20 mA Maximum load

) 4 mA 4.16 mA 4.19 mA 20 mA F E G PF2M701/702/705/710/750/711/721 PF2M725 Voltage output (0 to 10 V) 1 0 V 0.10 V 0.12 V 10 V 1: The analogue output current from the connected equipment should be 20 A or less when selecting 0 to 10 V.

The zero cut-off range is 0.0 to 10.0%F.S., and can be set in 1.0%F.S. increments. < Operation > Display [F14] by pressing UP or DOWN button in function selection mode. Press the SET button. Move on to select zero cut-off setting (flow rate).

Current consumption 55 mA or less Protection Polarity protection Power supply voltage for sensor 1 Power supply voltage: 1.5 V Power supply current for sensor 2 Max.110 mA (However, the total power supply current of 4 input is 440 mA or less maximum) The total power supply current when used as an IO-Link device is 200 mA or less maximum Display accuracy (Linearity) 5.0%F.S.

Connector pin numbers -18No.PS-OMX1005 Internal circuit and wiring examples ZSE20AF---Output specification -N NPN open collector 1 output Max. 28 V, 80 mA Residual voltage 1 V or less -P PNP open collector 1 output Max. 80 mA Residual voltage 1 V or less -A NPN open collector 2 outputs Max. 28 V, 80 mA Residual voltage 1 V or less -B PNP open collector 2 outputs Max. 80 mA Residual voltage

V, 80 mA Residual voltage 1.5 V or less When used as a switch output device Max. 80 mA Residual voltage 1.5 V or less -19No.PS-OMW0012-C Pressure Setting Default settings When the pressure exceeds the set value, the switch will be turned on.

Current consumption 55 mA or less Protection Polarity protection Power supply voltage for sensor Power supply voltage: -1.5 V Power supply current for sensor 1 Max. 50 mA (Max. 200 mA for total power supply current when sensor 4 input) Accuracy Display accuracy 0.5%F.S. 1 digit (at ambient temperature 253 oC) Repeatability 0.1%F.S.1 digit Temperature characteristics 0.5%F.S. (25 oC standard

Rated Flow Range: 06 (60 to 6000 l/min), Thread Type: F [G (ISO 1179-1 Compliant)], Port Size: 14 (1 1/2), Output Specifications: FS (Out: PNP; Func: Analog Current Output <-> External Input), Lead Wire: N (w/o Lead Wire and M12 Connector), Unit Specification: M (SI Unit Only), Calibration Certificate: A (Made to Order)

Rated Flow Range: 60 to 6000 l/min, Thread Type: F [G (ISO 1179-1 Compliant)], Port Size: 1 1/2, Output Specifications: Out: PNP; Func: Analog Current Output <-> External Input, Lead Wire: w/o Lead Wire and M12 Connector, Unit Specification: SI Unit Only, Calibration Certificate: Made to Order

Press the or button in function selection mode to display [F14]. Press the button. Move on to select zero cut-off setting.

Press the or button in function selection mode to display [F14]. Press the button. Move on to select zero cut-off setting.

Used as IO-Link device 18 to 30 VDC, including ripple (p-p) 10% Current consumption 25 mA or less Protection Polarity protection Switch output Select from NPN or PNP open collector output Max. load current 10 mA Max. applied voltage 30.0 V Residual voltage 1 V or less (at 10 mA) Short circuit protection Provided 2-screen (3-screen display available: sub display, 4 digits x 2) Main display